Wire & Cable
AWG Wire Size Chart
Diameter, area and resistance for every gauge, calculated from the AWG definition rather than transcribed. Includes maximum runs for a 5% impedance rule on speaker wire.
AWG is a formula, not a table: each step down multiplies diameter by 92^(1/39). Three gauge steps ≈ half the area; six steps ≈ half the diameter. 12 AWG copper is 1.588 Ω per 1000 ft.
| 4/0 | 0.4600011.6840 | 211600 | 107.219 | 0.0490 | 0.0804 | 0.0596 | |
|---|---|---|---|---|---|---|---|
| 3/0 | 0.4096410.4049 | 167806 | 85.029 | 0.0618 | 0.1013 | 0.0752 | |
| 2/0 | 0.364809.2659 | 133077 | 67.431 | 0.0779 | 0.1278 | 0.0948 | |
| 1/0 | 0.324868.2514 | 105535 | 53.475 | 0.0983 | 0.1611 | 0.1195 | |
| 1 | 0.289307.3482 | 83693 | 42.408 | 0.1239 | 0.2031 | 0.1507 | |
| 2 | 0.257636.5438 | 66371 | 33.631 | 0.1563 | 0.2562 | 0.1900 | |
| 3 | 0.229425.8273 | 52635 | 26.671 | 0.1970 | 0.3230 | 0.2396 | |
| 4 | 0.204315.1895 | 41741 | 21.151 | 0.2485 | 0.4073 | 0.3022 | |
| 5 | 0.181944.6213 | 33102 | 16.773 | 0.3133 | 0.5136 | 0.3810 | |
| 6 | 0.162024.1153 | 26251 | 13.302 | 0.3951 | 0.6476 | 0.4805 | |
| 7 | 0.144293.6650 | 20818 | 10.549 | 0.4982 | 0.8167 | 0.6058 | |
| 8 | 0.128493.2636 | 16510 | 8.366 | 0.6282 | 1.0298 | 0.7640 | |
| 9 | 0.114422.9063 | 13093 | 6.634 | 0.7921 | 1.2986 | 0.9633 | |
| 10 | 0.101902.5883 | 10383 | 5.261 | 0.9988 | 1.6375 | 1.2147 | |
| 11 | 0.090742.3048 | 8234 | 4.172 | 1.2595 | 2.0648 | 1.5318 | |
| 12 | 0.080812.0526 | 6530 | 3.309 | 1.5882 | 2.6036 | 1.9315 | |
| 13 | 0.071961.8278 | 5179 | 2.624 | 2.0027 | 3.2831 | 2.4356 | |
| 14 | 0.064081.6276 | 4107 | 2.081 | 2.5254 | 4.1400 | 3.0712 | |
| 15 | 0.057071.4496 | 3257 | 1.650 | 3.1844 | 5.2204 | 3.8727 | |
| 16 | 0.050821.2908 | 2583 | 1.309 | 4.0155 | 6.5828 | 4.8834 | |
| 17 | 0.045261.1496 | 2048 | 1.038 | 5.0634 | 8.3007 | 6.1579 | |
| 18 | 0.040301.0236 | 1624 | 0.823 | 6.3849 | 10.4670 | 7.7650 | |
| 19 | 0.035890.9116 | 1288 | 0.653 | 8.0512 | 13.1987 | 9.7914 | |
| 20 | 0.031960.8118 | 1022 | 0.518 | 10.1524 | 16.6432 | 12.3468 | |
| 21 | 0.028460.7229 | 810 | 0.410 | 12.8019 | 20.9868 | 15.5690 | |
| 22 | 0.025350.6439 | 642 | 0.326 | 16.1429 | 26.4638 | 19.6322 | |
| 23 | 0.022570.5733 | 510 | 0.258 | 20.3558 | 33.3702 | 24.7557 | |
| 24 | 0.020100.5105 | 404 | 0.205 | 25.6682 | 42.0791 | 31.2164 | |
| 25 | 0.017900.4547 | 320 | 0.162 | 32.3670 | 53.0608 | 39.3631 | |
| 26 | 0.015940.4049 | 254 | 0.129 | 40.8140 | 66.9084 | 49.6360 | |
| 27 | 0.014200.3607 | 202 | 0.102 | 51.4655 | 84.3699 | 62.5898 | |
| 28 | 0.012640.3211 | 160 | 0.081 | 64.8968 | 106.3885 | 78.9243 | |
| 29 | 0.011260.2860 | 127 | 0.064 | 81.8334 | 134.1534 | 99.5217 | |
| 30 | 0.010030.2548 | 101 | 0.051 | 103.1900 | 169.1644 | 125.4945 |
Resistance at 20°C unless noted. Sizes 4/0 through 30 AWG.
The definition
d(n) = 0.005 × 92^((36 − n) / 39) inch area (cmil) = (d in mils)² R = ρ × L / A ρ_Cu = 1.7241×10⁻⁸ Ω·m (100% IACS), ρ_Al = 2.8264×10⁻⁸ Ω·m (61% IACS), at 20°C
Gauge numbers run backwards — 4/0 is the largest, 30 among the smallest — because the number originally counted drawing passes, not size.
Speaker wire: the 5% rule
For audio, the usual criterion is keeping wire resistance under 5% of the speaker's impedance, so damping factor stays intact. That is an impedance-matching judgment, not a safety rule, so it is independent of electrical code:
- 12 AWG into 8 Ω — up to 126 ft one way
- 14 AWG into 8 Ω — up to 79 ft one way
- 16 AWG into 8 Ω — up to 50 ft one way
- 18 AWG into 8 Ω — up to 31 ft one way
Halve those lengths for 4 Ω speakers.
Voltage drop
L_max = (V × %drop/100) / (2 × I × R_per_ft)
The factor of 2 is the return conductor — a mistake worth avoiding, since forgetting it makes every run look twice as good as it is.
Data source and method
- Diameter
- Computed from the AWG definition above.
- Resistivity
- Annealed copper at 100% IACS (ASTM B3 / IEC 60028) and 1350-H19 aluminum at 61% IACS (ASTM B230). ASTM B258 defines the AWG diameters and areas, not resistivity.
- Verification
- Diameter and circular-mil area checked against six published gauges (4/0, 1/0, 10, 12, 14, 20); maximum deviation 0.15%. Resistance checked separately against the same six: 4/0 = 0.04901, 1/0 = 0.09827, 12 AWG = 1.588 Ω per 1000 ft, all within 0.03%.
- Deliberately absent
- Ampacity. See the notice above.
- Not code
- Voltage-drop figures are engineering calculations. Wiring must follow local code and be done by a licensed electrician.
Related charts
- Sheet metal gauge chart — the other gauge system, and why aluminum sheet uses this same AWG formula
- Pipe size chart — for conduit sizing alongside conductor sizing